- Master/slave CPU by redundant control module
- Combinable loop/spur technology with decentralized intelligence
- Freely configurable functionality of modules
- 4 free programmable potential free or monitored potential driving contacts and 1 output for alarm transmission unit (ATU)
- Increased security and reliability via emergency mode function of the loop modules
- Emergency mode for monitored areas up to 48,000 m² or more than 512 fire detectors acc. to the German Planning standard VDE 0833 and/or VdS 2095.
- USB, 2 x RS 485, TTY interfaces onboard
- Direct output of the proprietary EDP communications protocol (Data Protocol) via interface RS 485
- Operation of loop-powered alarm signaling devices (optical/acoustic/voice) in different alarm zones via esserbus-PLus
- Cascadable power supply up to 450 W according to EN 54-4
- Loop length up to 3.5 km (esserbus)
- Up to 1,000 control zones and detector zones
- Operation of different input/output gateways
- Integrated interfaces for operation of required fire brigade periphery, e.g. fire brigade indicating panel, fire brigade operating unit
- Event memory with 10,000 entries
- Operation of VdS approved wireless components with convenient radio signal intensity measurement
- Parameterization, calibration and programming directly via USB interface
- Galvanic isolation of analog loops possible
In connection with display and operating unit (Part No. FX808324)
- Display and operating unit with 5.7" TFT display
- Capacitive keyboard for touch-sensitive operation
- Program-controlled night design with interactive, user-configurable keyboard menu
Additional features for powered loop
- BUS supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 - 3 with alarm tone as per DIN 33404
- Up to 48 powered loop base sounders (series 9200) per loop
- Up to 8-64 powered loop IQ8Alarm+ per loop
- Up to 48 IQ8Quad with alarm device per loop
Additional Information:
Optionally: display and operating unit (Part No. FX808324) or neutral front (Part No. FX808325) must be ordered separately.
Compatible serial printers FlexES: Part No. FX808353, FX808354, FX808353.INT, FX808354.INT
Max. 10 modules, up to 10 esserbus analog loops and expandable up to 127 loop devices (per loop) in mixed mode / loop powered and non-loop powered (system supports up to 1,270 digital loop addresses in total).
Scope of Delivery:
Basic set includes: 1 x power supply module, 1 x PS connection module, connection cable 0.6 m, 1 x rear panel 2, 1 x control module, 1 x housing frame and 1 x base module carrier1 x set air filter