FACP FlexES Control FX18, 5 loops

FX808395

Approval: VdS, CNBOP

VdS system authorization: S 209207

Hardware FlexES Control FX18 basic configuration, with software support for 5 loops. System supports up to 635 digital loop addresses in total. Configuration is modularly expandable up to 18 loops by exchange of the CPU license.
  • Master/slave CPU by redundant control module
  • Combinable loop/spur technology with decentralized intelligence
  • Freely configurable functionality of modules
  • 4 free programmable potential free or monitored potential driving contacts and 1 output for alarm transmission unit (ATU)
  • Increased availability via emergency mode func­tion of the loop modules
  • Emergency mode for monitored areas up to 48,000 m² or more than 512 fire detectors acc. to the German Planning standard VDE 0833 and/or VdS 2095
  • USB, ERS 485, TTY interfaces onboard
  • Direct output of the proprietary EDP communications protocol (Data Protocol) via interface RS 485
  • Operation of loop-powered alarm signaling devices (optical/acoustic/voice) in different alarm zones via esserbus-PLus
  • Cascadable power supply to 450 W according to EN 54-4
  • Loop length up to 3.5 km (esserbus)
  • Operation of different input/output gateways
  • Integrated interfaces for operation of required fire brigade periphery, e.g. fire brigade indicating panel, fire brigade operating unit
  • Event memory with 10,000 entries
  • Operation of VdS approved wireless components ​with convenient radio signal intensity measurement
  • Parameterization, calibration and programming directly via USB interface
  • Galvanic isolation of analog loops possible
  • Up to 1,000 control zones and detector zones


In connection with display and operating unit (Part No. FX808324)
  • Display and operating unit with 5.7" TFT display
  • Capacitive keyboard for touch-sensitive operation
  • Program-controlled night design with interactive, user-configurable keyboard menu


Additional features for powered loop
  • BUS supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 - 3 with alarm tone as per DIN 33404
  • Up to 48 powered loop base sounders (series 9200) per loop
  • Up to 6-18 powered loop IQ8Alarm+ per loop
  • Up to 48 IQ8Quad with alarm device per loop


Additional Information:

Optionally: display and operating unit (Part No. FX808324) or neutral front (Part No. FX808325) must be ordered separately.

Compatible serial printers FlexES: Part No. FX808353, FX808354, FX808353.INT, FX808354.INT

Max. 18 modules, up to 18 esserbus analog loops and expandable up to 127 loop devices (per loop) in mixed mode / loop powered and non-loop powered (system supports up to 2,286 digital loop addresses in total).

Scope of Delivery:

Basic set includes: 1 x power supply module, 1 x plugin connection cable,1 x PS connection module, connection cable 0.6 m, 1 x rear panel 1, 1 x control ​module, 1 x housing frame and 1 x base module carrier, 1 x set air filter, 1 x set air filter

Rated voltage VAC
230 V AC
Rated frequency
50 ... 60 Hz
Rated current
0.8 A
Output voltage 24 V DC
Quiescent current approx. 192 mA (base model w/o display and operating unit)
approx. 348 mA (base model with display and operating unit)
Current consumption for ext. devices
3 A
Battery capacity 4 x 12 V / 26 Ah
Ambient temperature
5 °C ... 45 °C
Storage Temperature -10°C ... 50°C
Air humidity
< 95 % (non-condensing)
Type of protection
IP 30
Housing ABS, 10% glass fiber reinforced, V - 0
Color
gray, similar to Pantone 538
Weight approx. 15.1 kg (incl. neutral front)
approx. 17 kg (incl. operating unit)
Dimensions
W: 450 mm H: 960 mm D: 185 mm
Declaration of Performance DoP-20903130701