IQ8MCP electronic module w/o isolator, with relay

804906

Approval: VdS, CNBO

Addressable electronic module with floating contacts of a changeover relay NC/C (break) or NO/C (make), suitable for use in the esserbus and powered loop with alarm latch and alarm indicator. Without BUS connection, the detector operates as conventional manual call point.
Without built-in loop isolator and optional connection for conventional manual call point.

The relay output is activated with the triggering of this detector. The relay output can be programmed in the System 8000 and IQ8Control fire alarm control panel customer data as a control group with freely programmable trigger functions.

CNBOP certificate valid only with additional "Pozar" sign available as option (Part No. 704911).
Additional Information:
Take note, for a LARGE MCP you have to order the electronic module and the MCP housing separately to have a complete MCP.