IQ8Alarm Plus/FSp combined Voice Sounder and Visual Alarm Device (VAD) EN 54-23 cat. W, red flash

807372RR

Addressable, completely bus supplied and short circuit / open circuit resilient combined voice sounder and Visual Alarm Device (VAD) in compliance with EN 54‑3 & EN 54‑23 with integrated voice messages, signaling tones and red light flash for acoustic and optical alarm signaling.
With up to 20 different programmable signaling tones including DIN tone in accordance with DIN 33404 Part 3.
Speech alarm with 5 pre-programmed alarm messages in 5 different languages.
The volume can be set to 8 different levels.
Selection or combination of speech messages and signaling tones as well the volume control are carried out via the tools 8000 programming software.
The optical signaling device is suitable for square signal ranges W‑2.4‑5 to W‑3.6‑8.
The optical signal range is adjustable in 6 sizes via tools 8000.
Signaling device with flat base, suitable for wall mounting.
Optionally, IP base Part No. 806202 with side cable entry and weatherproof protection can be installed.


Same as 807322W, but with an individual combination of up to 5 languages, see special order form in the appendix.

Addressable, completely bus supplied and short circuit / open circuit resilient voice sounder in compliance with EN 54‑3 with integrated voice messages and signaling tones for acoustic alarm signaling.

With up to 20 different programmable signaling tones including DIN tone in accordance with DIN 33404 Part 3.

Speech alarm with 5 pre-programmed alarm messages in 5 different languages.

The volume can be set to 8 different levels.

Selection or combination of speech messages and signaling tones as well the volume control are carried out via the tools 8000 programming software.

Signaling device with flat base, suitable for wall and ceiling mounting.

Optionally, IP base Part No. 806201 with side cable entry and weatherproof protection can be instalSame as 807322W, but with individual text and/or sounds. The maximum recording time per device is 169 seconds.
Addressable, completely bus supplied and short circuit / open circuit resilient voice sounder in compliance with EN 54-3 with integrated voice messages and signaling tones for acoustic alarm signaling.

With up to 20 different programmable signaling tones including DIN tone in accordance with DIN 33404 Part 3.

Speech alarm with 5 pre-programmed alarm messages in 5 different languages.

The volume can be set to 8 different levels.

Selection or combination of speech messages and signaling tones as well the volume control are carried out via the tools 8000 programming software

Signaling device with flat base, suitable for wall and ceiling mounting.

Optionally, IP base Part No. 806201 with side cable entry and weatherproof protection can be installed.

Same as 807322W, but with individual text and/or sounds. The maximum recording time per device is 169 seconds.

Addressable, completely bus supplied and short circuit / open circuit resilient voice sounder in compliance with EN 54-3 with integrated voice messages and signaling tones for acoustic alarm signaling.

With up to 20 different programmable signaling tones including DIN tone in accordance with DIN 33404 Part 3.

Speech alarm with 5 pre-programmed alarm messages in 5 different languages.

The volume can be set to 8 different levels.

Selection or combination of speech messages and signaling tones as well the volume control are carried out via the tools 8000 programming software

Signaling device with flat base, suitable for wall and ceiling mounting.

Optionally, IP base Part No. 806201 with side cable entry and weatherproof protection can be install

Addressable, completely bus supplied and short circuit / open circuit resilient combined fire alarm sounder and Visual Alarm Device (VAD) in compliance with EN 54-3 & EN 54-23 with integrated signaling tones and red light flash for acoustic and optical alarm signaling.

With up to 20 different programmable signaling tones including DIN tone in accordance with DIN 33404 Part 3.

The volume can be set to 8 different levels.

The optical signalling device is suitable for square signal ranges W-2.4-5 to W-3.6-8.

The optical signal range is adjustable in 6 sizes via tools 8000.

Signaling device with flat base, suitable for wall mounting.

Optionally, IP base Part No. 806202 with side cable entry and weatherproof protection can be installed.

  • Completely bus supplied alarm device
  • Powered loop compatible
  • Low power consumption
  • Up to 13 alarm devices for each powered loop
  • Each alarm device has built-in isolator
  • Synchronous trigger
Optical alarm properties
  • EN 54-23 compliant
  • W category
  • Signal range up to 8.0 m room width for wall mounting
  • Room size configurable via tools 8000
Acoustic alarm properties:
  • EN 54-3 compliant
  • High acoustic pressure
  • Volume programmable in 8 steps via tools 8000
  • 20 different signaling tones, including DIN tone
  • Multilingual speech alarm in 5 different languages
  • Alarm signaling, evacuation, and test alarm can each be programmed in different languages
  • Speech alarm, 5 pre-programmed alarm texts and other country-typical alarm signals
Additional Information:
  • Replacement for Part No. 807372
  • To change the factory settings for EN 54-23 square signal ranges programming software tools 8000 from version V1.24 is required.

Common technical data:


Quiescent current @ 19 V DC
approx. 55 μA
Quiescent current @ FACP battery
approx. 300 μA @ 42 V
Operating voltage
14 ... 42 V DC (via powered loop)
Ambient temperature
-10 °C ... 55 °C
Storage temperature
-25 °C ... 75 °C
Type of protection
IP 43*2
IP 56 with IP base 806201*3
Housing
Polycarbonate plastic
Air humidity
< 95 % (non-condensing)
Color
red, similar to RAL 3020
Calotte: translucent / partially frosted
Weight
approx. 300 g (with base)
Loadfactor total
7 *1 ... 11.9
Dimensions
Ø: 112 mm D: 78 mm
Ø: 112 mm D: 93 mm (with IP base)
Declaration of Performance
DoP-21431171215

Acoustic:

Load factor acoustic
4
Sound level
90 db(A) +/- 2 dB @ 1 m / @ 90° / @ DIN tone, for speech & tone
97 db(A) +/- 2 dB @ 1 m / @ 90° / @ DIN tone, only tone
Specification
EN 54-3: 2001 / A1: 2002 / A2 : 2006 / -17: 2005
EN 54-3 Sounder
EN 54-3 Voice Sounder

Optic:

Load factor optic
3 *1 ... 7,9
Frequency of flash
approx. 0.5 Hz *1 /1 Hz
Flash color
red
Luminous intensity
approx. 6,6 cd eff. *1 / max. 17 cd eff. @ W-3,6-8

Signal range
W-2,4-5 / 60 m³ *1 (factory) … W-3,6-8 / 230 m³
Mounting
Wall
Specification
EN 54-23: 2010 / -17: 2005

*1 Factory setting, configuration with service- and programming software tools 8000
*2 IP 21C acc. EN 54-3 / -23
*3 Do not use the base for acoustic alarm applications in compliance with EN 54-3

  • 806202 IP base, red