IQ8MCP compact, small, red, with resettable element

804973

Approval: VdS

Same as 804971, but with plastic triggering element, which supports easy reset after an alarm has been triggered without having to replace the broken element (glass pane). Typically applied in nursery, clean rooms as for example in food processing industries.
Additional Information:
If the glass pane is replaced with the optionally available plastic pane with reset function, the MCP can be reset from the outside using the key. For the surface mounting of the MCP the surface mount base Part No. 704980 must be ordered separately, if the cable wasn't laid about a standard flush mount wall socket. Type a definition - single action in accordance with EN 54-11 § 3.4.1 (excerpt taken from EN standard): Manual fire alarm unit, for which the alarm status is automatically set (additional alarm triggering is not required) after the fragile element has been broken or its position has been changed.

Scope of Delivery:
1x Plastic operating panel 704964
1x Key 704966
1x Multilingual paper insert with "Out of order" pictogram included
Alarm displayred LED and yellow actuation indicator
Alarm current w/o communication curtainapprox. 18 mA
Connection terminalmax. 2.5mm² (AWG 26-14)
Application temperature-20 °C ... 70 °C
Operation indicatorLED, green
Operating voltage8 ... 42 V DC
Colorred, similar to RAL 3020
HousingASA plastic
Weight gapprox. 110 g
Storage temperature-30 °C ... 75 °C
No. of detector/zonemax. 127 MCP per loop
Detector specificationEN 54-11, type A
Air humidity< 95 % (non-condensing)
Quiescent current @ 19 V DCapprox. 45 μA
Type of protectionIP43 (in housing)
VdS classF
VdS-NrG 205132
DimensionsW: 88 mm H: 88 mm D: 57 mm (with surface mount housing)
  • 704980 Surface mount housing