Optical smoke detector ES Detect

800371

Approval: G 213066

Scattered-light smoke detector for reliable early detection of fires. Fire detector with decentralized intelligence, automatic function self-test, automatic environmental adaptation, alarm and operating data storage and alarm display. A remote indicator can also be connected.
System benefits:
  • Optimally matched to the ES Line system.
  • With multisensor detectors for the detection of all fires, even under the most difficult operating conditions
  • Up to 30 detectors per detection group.

Reliable detection:
  • Uniform response sensitivity of the detector for all different types of fire for the multisensor detectors
  • Large distance between signal and interference magnitudes due to special sensor and electronics design for suppressing electromagnetic influences
  • Automatic adaptation to varying environmental influences
  • Electronic compensation of long-term influences of contamination or aging

Reliable false alarm suppression:
  • High reliability against false alarms by temporal evaluation of different sensor criteria
  • Exclusion of signal forms not typical of fires through special filter algorithms
  • Automatic self-monitoring of the detector electronics
  • Automatic self-monitoring of sensors for function and condition

Maintenance:
  • Designation of the heat detector by a black ring on the light pipe
  • Hours of operation, alarm and fault counter in each detector
  • Operation data retrieval of all detectors of a group with standard service PC and field bus interface
  • Detector LED for alarm display and as an identification display in the service (for maintenance with 8000 tools)

Wide range of accessories:
  • Standard socket and relay base
  • Socket adapter for ceiling installation
  • Dust caps optional for fire detectors and detector base
  • Kit for suspended mounting

Additional Information:
Special colors on request! In order to pass through existing wires, the WAGO grips (e.g., type 243-204 (O 0.5-1 mm) or 273/104 (0.75-2.5 mm²)), can be integrated into the detector base.

Scope of Delivery:

Detector base is not supplied as standard
Alarm current @ 9 V DCtyp. 9 mA
Application temperature-20 °C ... 72 °C
Operating voltage8 ... 42 V DC
Colorwhite, similar to RAL 9010
Weight gapprox. 110 g
Storage temperature-25 °C ... 75 °C
Air velocity0 ... 25.4 m/s
MaterialABS
Detector specificationEN 54-7
Rated voltage VAC9
Air humidity< 95 % (non-condensing)
Quiescent current @ 9 V DCapprox. 30 μA
Type of protectionIP 43 (base + option)
Area to be monitoredmax. 110 m²
Height to be monitoredmax. 12 m
Dimensionsø: 117 mm H: 49 mm (62 mm inkl. Sockel)
  • 767800 assembly bracket
  • 805590 standard IQ8Quad detector base
  • 805591 detector base with IQ8Quad relay contact