Explosion-proof conventional MCP, IP66

761697

Approval: VdS, PTB 97 ATEX 3197

Explosion-proof encapsulated conventional manual call point for hazardous areas in conformity with EN 54-11 Type B for the manual actuation of a fire alarm and/or a hazard alarm, as a detector for usage in explosion-hazardous areas both inside and outside.

The operating front foil has been designed as a double-sided insert. Complementary to the symbolism conforming to the standards for manual call points in compliance with EN 54-11 (Type B), it has a symbol and multilingual text on the back for the "out-of-order" status of the detector and is always available for possible maintenance work.

The labeling foil of the manual call point also has a double-sided design. In compliance with EN 54-11, it contains the standard symbol of a burning house. On the back, the symbol is supplemented with the word “FIRE” (multilingual).
Additional Information:
Please note, an allen key (size 4) is needed for opening and resetting the manual call point, and is not included in the scope of delivery.

Scope of Delivery:
1 x Glass pane 704910
1 x Kit of double-sided operating front foil (with "out-of-order" on the back)
1 x Kit of double-sided labeling foil (multilingual)
Operating voltage 12 ... 24 V DC
Alarm current approx. 9mA
No. of detector/zone max. 10 detectors per Zone (according to VdS)
Application temperature -55 °C ... 65° C
Storage temperature -55 °C ... 85° C
Explosion protection Ex e d mb IIC T6, T5
Connection terminal 0.6 mm ... 4 mm²
Type of protection IP66
Housing Glass fiber reinforced polyester resin
Air humidity < 95 % (non condensing)
Color red, similar to RAL 3000
Weight approx. 1.8 kg
Detector specification DIN 14678 Form K
Dimension W: 136 mm H: 138 mm D: 88mm
  • 704910 Spare glass pane for MCP housings
  • 961650 Cable gland