- One contact input and one floating relay output
- Voltage supply via the field bus
- Test and reset function
- Higher IP protection
- Programmable inverse monitoring functionality of the contact input
- Total cable length of the monitoring input line up to 500 m
- Integrated loop isolator
- Max. 127 transponder TAL electronic modules per analog loop
- DC/AC load switching by relay output
Additional Information:Please note that for surface mounting, the mount housing (Part No. 704981) must be ordered separately. Compatible with all IQ8Control systems with firmware V3.08 and tools 8000 V1.14 or superior.
Scope of Delivery:2 x 10 k (terminating), 1 x 1 k (alarm), 1 x 6.8 k (inverse operation)