esserbus alarm transponder, 4 IN/2 OUT with isolator

808623

Approval: VdS

The esserbus transponder functions as a device on the multi-functional primary line. The connection of four zones with automatic standard detectors, manual call points (non-addressable) as well as special detectors is possible. In addition, two programmable relay outputs are also available.
Both relay outputs of the transponder may be used to reset a connected third-party detector. The reset function relates to the corresponding special detector, e.g. by switching the appropriate input to GND or by a short interruption of the detectors supply voltage. Therefore the control mode >Reset-Relay< as well as the desired relay operation mode (normally closed or open) must be configured with the programming software tools 8000 from V1.15 and above. The relay output will be activated for the selected reset time (1 to 14 seconds) if the assigned input (G1 for relay 1/G2 for relay 2) of the transponder is reset. Refer to the detectors manual for the required reset time.

Monitoring via the EOL terminating devices (Part No. 808624/808626) is required for the connection of fire detectors and for the controlling of alarm signaling devices. The enclosed resistors can be used to connect the floating contacts.

The esserbus alarm transponder requires an external voltage supply. An optional Voltage Converter (Part No. 781336) is also required for 12V DC operation. The esserbus alarm transponder external voltage supply can be monitored during operation.

The EOL-I terminating device (Part No. 808626) must be used for standard-compliant monitoring of detector zone inputs. The EOL-O (Part No. 808624) must be used for standard-compliant monitoring of connected alarm signaling devices.
  • Only one loop address is needed per transponder
  • Digital inputs
  • Integrated loop isolator
  • Conventional connection of standard fire detectors and signaling devices
  • Loop monitoring in compliance with EN 54-13
  • Integrated loop isolator
  • Programmable relay outputs
  • Programmable relay reset function
  • Max. 100 transponders per FACP
  • Max. 31 transponders per loop
  • Max. 127 detector zones per loop
  • Detector numbers per zone input of the transponder:
  • Max. 30 conventional detectors (without SOC)
  • Max. 10 conventional detectors (with SOC)
  • Max. 10 Manual call points (MCP)
  • Max. 10 Technical Alarm Modules (TAM)
  • Max. 5 audible alarm devices per each output (observe calculation table in tools 8000)

Scope of Delivery:
Installation accessory pack
Operating voltage10 ... 28 V DC
CE certificate0786-CPD-20947
Weight gapprox. 28 g
Contact load relay30 V DC / 1 A
Storage temperature-25 °C ... 75 °C
Length conductor cable #1max. 1000 m
Air humidity< 95 % (non-condensing)
Relay monitoringEOL-O (or 10 kƒ / ± 40% for unmonitored activation)
Quiescent current @ 12 V DCapprox. 12 mA
Type of protectionIP 40 (in housing), IP55 (with high IP housing)
SpecificationEN 54-17 : 2005
Current consumptionmax. 120 mA @ 12 V DC
Ambient temperature-10 °C ... 50 °C
VdS-NrG 210020
DimensionsW: 82 mm H: 72 mm D: 20 mm
  • 788603.10 Module housing for snap-on mounting rail
  • 788600 Housing surface mount, gray
  • 788650.10 Housing surface mount, white
  • 788601 Housing flush mount, gray
  • 788651.10 Housing flush mount, white
  • 788655 High IP housing base
  • 788656 High IP housing
  • 808624 EOL-O Terminating device
  • 808626 EOL-I Terminating device